• ADM loop technology with
System Sensor/200 protocol
• Combination of optical and thermal
characteristics of fire
• Two self-learning and three fixed
sensitivity levels
• Thermal-only operation
• Constant response sensitivity
• Function testable with magnet
Description
The addressable Multisensor 2251TEM uses the
scattered light principle as well as a separate thermal
detection unit. It was developed to detect the charac-
teristics of fire in a wide range of applications, and to
avoid deceptive alarms. The modern design of both
measurement systems and the analysis of the parame-
ters by means of a special algorithm allow to reliably
evaluate the characteristics of fire.
cation between the fire detection control panel and the
detector. That ensures a periodical function testing of
the detector.
The influence of contamination on the optical measu-
rement system is compensated for by using intelligent
evaluation algorithms. With that, the response sensiti-
vity of the detector is kept constant for a long time –
a further effective step to avoid false alarms.
The sensitivity of the detector can be individually adjus-
ted in 5 steps between 1.5%/m and 5.2%/m according
to the application. Three steps have a fixed sensitivity,
whereas two self-learning steps automatically adjust the
sensitivity to short-term changes of the environmental
conditions. Furthermore, the optical detection unit can
be completely disabled for a thermal-only operation.
The two LEDs with 360° visibility indicate the activated
condition of the detector. The detector address is se-
lected with two decadic rotary switches, thus allowing
to change the detector without additional tools.
A detector function test can be conveniently conducted
using a magnet. The detector can be attached to va-
rious bases and it can be protected against theft.
The proven ADM loop technology with System Sen-
sor/200 protocol establishes a permanent communi-
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
2251TEM_DBL_LST_EN_0819.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
LaCie Computer Drive Hard Disk MAX User Manual
Lanzar Car Audio Car Stereo System VBD1800 User Manual
Lumens Technology Projector HD72 User Manual
Makita Chainsaw UC3030A User Manual
Makita Cordless Saw 50008MGA User Manual
Makita Impact Driver BTD061 User Manual
Makita Sander 9401 User Manual
Makita Trimmer UH4510A User Manual
Maytag Microwave Oven MMV5208WB User Manual
Metrologic Instruments Scanner Laser Scanner User Manual