Optical Smoke Detector
• Addressable conventional technology
• Sensitivity selectable in 3 steps
• Addressing by means of address
module or detector parameterisation
• Remote readout of detector condition
• Extremely flat design
• Function testable with Remote Test
Unit ECO1000RTU
Description
The Optical Smoke Detector 2351E uses the scattered
light principle, and was developed for the detection of
smoke particles in a wide range of fire detection applica-
means of the Remote Programming and Test Unit, is
displayed on the Zonal Display Unit S300ZDU.
tions. The modern design of the measurement chamber A test activation of the detector can be carried out
allows to reliably evaluate the characteristics of fire.
using the Remote Test Unit ECO1000RTU. In addition to
the test activation of the detector, the Remote Program-
An internal drift compensation adjusts the alarm thres- ming and Test Unit S300RPTU can also be used to set
hold by continually evaluating the contamination of the and display the following detector parameters:
detector. With that, the sensitivity of the detector is kept • the sensitivity in 3 levels,
constant for a long time.
• the detector address, and
• the date of the previous maintenance.
Addressable conventional technology is used for alarm Furthermore, the degree of drift compensation (detec-
transmission to the fire detection control panel. The de- tor contamination) and the current condition of the de-
tector addressing can be achieved in 2 ways:
tector can be read out.
• A detector with an Address Module NG58-1 can be
individually identified by the suitable control panel.
The detector can be attached to various detector bases
• An address, which has been stored in the detector by and it can be protected against theft.
Specifications
Operating voltage
Current consumption
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 75µA (quiescent)
-30°C to +70°C
5 – 95% (no condensation)
102 × 32.5 (mm)
cream
Weight
75g
Approval
VdS G202012
Order number
Order name
241040
Optical Smoke Detector/Conv./300/SS 2351E
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
2351E_DBL_LST_EN_0804.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
KWC Stereo Amplifier 802 141 User Manual
Kyocera All in One Printer FS 1028MFP User Manual
Lenovo Computer Monitor L171p User Manual
Lenovo Computer Monitor T540 User Manual
Lenoxx Electronics Furnace G60DFX User Manual
Lightolier Indoor Furnishings VRA2G12LS232 User Manual
Linksys Network Card WUSB100 ver 2 User Manual
Lochinvar Boiler A05H00172528 User Manual
Maxtor Tool Storage 20274700 User Manual
Meyer Sound Car Speaker UP 4XP User Manual